READ THROUGH CAREFULLY BEFORE ATTEMPTING INSTALLATION
|
The Door Holder Control Unit as described below has been designed to operate a single Door Holder Electro-Magnet in accordance with British Standard BS 5839. The control unit when connected to a 110 or 220/240 mains supply provides a nominal 24vDC output that is connected to the door holder electro-magnet assembly via. normally closed contacts of a relay that is operated from a fire alarm sounder circuit. |
![]() |
(Read in conjunction with Wiring Diagram below)
In the Normal (non alarmed) state the door holder control unit supplies a continuous 24vDC supply to the door holder which being energised will hold the door open.
When the fire alarm operates, its sounder lines are energised from the fire alarm control panel. This voltage operates a relay in the Door Holder Control unit changing over its contacts. The door holder 24v supply is therefore interrupted which demagnetises the door holder magnet and the door is released.
A bridge rectifier is incorporated in the door holder control unit sounder circuit which eliminates the need to observe sounder polarity of these connections to the unit and also allows the use of the unit on two stage reverse polarity sounder circuits.
NOTE: If connecting to a single stage system, the sounder line monitoring voltage must be checked. If this exceeds 5v.d.c., a diode type 1N4002 or equivalent must be connected between the positive sounder line and TBB2. This is to prevent relay operation by the monitoring voltage.
|
Connect as shown opposite. |
![]() |
1. The EPL19010 control unit is only suitable for switching 1 door holder that requires continuous supply availability.
2. Other models are available to control more than 1 door holder and to operate from 12 and 50v.d.c. sounder lines.
8. Test the system as follows.
It is important that the Installation Card supplied with this equipment is completed and posted as soon as the equipment is installed. This will ensure that both user and installer are kept informed of equipment modifications etc.
For further information or technical assistance contact as below,
Evasafe Products Limited, Farren Court, Cowfold, Horsham, West Sussex, RH13 8BP.
Telephone 01403 864 676, Fax 01403 864 873, email: info@evasafe.co.uk
Copyright Evasafe Products Limited 1999-2006